The DINGXING Three-Phase Pad-Mounted Transformer (also known as an American Box-Type Transformer or combined transformer) is a new-generation distribution product specially designed for modern power distribution networks, developed by absorbing advanced international technology and design concepts. With a primary voltage class of up to 35 kV, it integrates the transformer, high-voltage load switch and fuse protection in a single compact, fully sealed enclosure.
Its fully sealed, fully insulated structure provides reliable personnel protection, while the compact design occupies only about 1/3 of the footprint of a European-type transformer of the same capacity — flexible and convenient to install, in either ring-network or terminal configurations.
75kva
1250kva
2250kva
4500kva|
Parameter |
Value |
|
Base kVA Ratings |
45 / 75 / 112.5 / 150 / 225 / 300 / 500 / 750 / 1000 / 1250 / 1500 / 1750 / 2000 / 2250 / 2500 / 2750 / 3000 / 3750 / 5000 kVA |
|
Maximum Voltage |
Up to 35 kV |
|
Frequency |
50 Hz or 60 Hz |
|
Cooling Class |
ONAN or KNAN |
|
Temperature Rise |
55°C, 65°C or 55/65°C |
|
Winding Material |
Copper or Aluminum |
|
Core Material |
Silicon steel (3-legged or 5-legged) |
|
Fluid Options |
Type II Mineral Oil or Envirotemp™ FR3™ (vegetable oil) |
|
Phase Configuration |
Available in Δ (Delta) or Y (Wye) |
|
Standards |
IEEE, DOE, NEMA, IEC, CSA + custom requirements |
|
Tap Changer Type |
Off-load and load tap changers |
|
Parameter |
Specification |
|
High Voltages (HV) |
4160GrdY/2400 V through 34500GrdY/19920 V; 2400 V through 34500 V Delta; various dual high voltages |
|
High Voltage Taps |
All voltages available with 5 or 7 step taps; dual voltage taps provided only on the higher voltage |
|
Low Voltages (LV) |
208Y/120 V, 480Y/277 V, 480 V, 240 V, 240 V with 120 V mid-tap in one phase; 4160Y/2400 V, 4160 V, 2400 V |
|
Primary Insulation Classes |
35 kV, 200 kV BIL and below |
|
Parameter |
Specification |
|
High Voltages (HV) |
12470GrdY/7200 V through 34500GrdY/19920 V; 4160 V through 34500 V Delta; various dual high voltages |
|
High Voltage Taps |
All voltages available with 5 or 7 step taps; dual voltage taps provided only on the higher voltage |
|
Low Voltages (LV) |
480Y/277 V, 480 V, 240 V; 4160Y/2400 V, 4160 V, 2400 V |
|
Impedance Guidelines |
300–500 kVA: 2.8–5.0% nominal · 750–2500 kVA: 5.75% nominal · 3000–7500 kVA: consult factory |
|
Parameter |
Options |
|
HV Bushing Config |
Dead front or live front; loop feed or radial feed |
|
Fluid Options |
Type II Mineral Oil; Envirotemp™ FR3™ vegetable oil |






















Q1. What is a pad-mounted transformer? A pad-mounted transformer is a ground-mounted, fully sealed distribution transformer installed on a concrete pad. Also known as an American box-type transformer, it connects directly to medium-voltage underground distribution cables and is widely used in commercial centers, residential areas and public facilities.
Q2. What capacity range does the DINGXING pad-mounted transformer cover? The series covers 19 base ratings from 45 kVA to 5000 kVA, with primary voltage classes up to 35 kV.
Q3. What is the difference between dead-front and live-front bushings? Dead-front bushings use fully insulated, separable elbow connectors that can be operated safely with 200 A load current, protecting personnel from live parts. Live-front bushings expose terminated conductors and require approach clearances. Both configurations are available, in loop-feed or radial-feed arrangements.
Q4. What fluid options are available? Type II mineral oil for standard applications, or Envirotemp FR3 vegetable-based oil for enhanced fire safety (higher flash point) and environmental friendliness in eco-sensitive installations.
Q5. Can the transformer be used in a ring network? Yes. The unit can operate in a ring network or as a terminal transformer, with convenient conversion between the two modes to improve power supply reliability. Cable connectors operate with 200 A load current.
Q6. What switch options are available? 2-position or 4-position LBOR (load-break oil rotary) switches with V-blade or T-blade, plus 2-position LBOR switches. An electrically operated load switch is optional to meet distribution-automation requirements.
Q7. What standards does the transformer comply with? The transformer is designed and tested to IEEE, DOE, NEMA, IEC and CSA standards, as well as customer-specific requirements.
Q8. What are the impedance guidelines? 300–500 kVA units: 2.8–5.0% nominal. 750–2500 kVA units: 5.75% nominal. For 3000–7500 kVA ratings, consult DINGXING Electric for a custom design.